GT-2744

Digital output

  • 4 digital outputs
  • 24/48/110VDC, 240VAC
  • Relay Normally open (NO), Form A, SPST
  • Max 2A (load dependent)
  • 10pt removable terminal block

Facts

General description

Article number 100-8010
Warranty 2 year
Article status Active
Shock operating IEC 60068-2-27 (15G)
Vibration resistence Sine vibration (based on IEC 60068-2-6), 5 ~ 25Hz: ±1.6mm, 25 ~ 300Hz: 4G, Sweep rate: 1 octave/min., 20 cycles, Random vibration (based on IEC 60068-2-64), 10 ~ 40Hz: 0.0125g²/Hz, 40 ~ 100Hz: 0.0125 → 0.002g²/Hz, 100 ~ 500Hz: 0.002 g²/Hz, 500 ~ 2000Hz: 0.002 → 1.3 x 10-4g²/Hz, Test time: 1hrs for each test
Industrial emissions EN 61000-6-4/A11: 2011
Industrial immunity EN 61000-6-2:2005
Horisontal, Vertical
Product certifications CE, UL, FCC, RoHS, China RoHS, Reach
Power dissipation Max. 35mA @ 5VDC
Isolation I/O to Logic: Photocoupler isolation, I/O to Field Power: Non-Isolation
Field power Not used. Field power bypassed to next expansion module.
Weight 40g
Module size 12x99x70mm

Environmental

Mounting 35mm DIN rail
Operating temperature -40 ~ 70℃, Degraded performance > 60℃
Storage temperature -40 ~ 85℃
UL temperature -20 ~ 60℃
Relative humidity 5 ~ 90% non-condensing

Digital output module specifications

Indicators 4 green output status
Outputs per module 4 point relay
Output current rating 2.0A @ 0 ~ 32VDC, 0.8A @ 48VDC, 0.5A @ 110VDC, 2.0A @ 240VAC, -40 ~ 70℃ (2A load 2ch), -40 ~ 60℃ (2A load 4ch)
Output signal delay OFF to ON: Max. 5ms @ 24VDC, ON to OFF: Max. 8ms @ 24VDC, OFF to ON: Max. 5ms @ 220VAC, ON to OFF: Max. 15ms @ 220VAC
Output voltage range 0 ~ 32VDC @ 2.0A resistive load, 48VDC @ 0.8A resistive load, 110VDC @ 0.5A resistive load, 240VAC @ 2.0A resistive load
Relay type 1 pole NO (SPST)
Frequencey range 47 ~ 63Hz
Expected contact life 20M cycles (resistive load)
Common type 4 points / 2 COM

Limited availability

GT-2744

Digital output


EOL - End Of Life:
-

LTB - Last Time Buy:
-

LTD - Last Time Delivery:
-

LTR - Last Time Repair:
-

Replacement Parts: