GT-1428

Digital input/output

Diagnostics
  • 8 digital inputs/outputs
  • 24 VDC
  • IN SINK/OUT SOURCE
  • 18pt removable terminal block
Contact Print (PDF)

Facts

General description

Article number 100-8121
Warranty 2 year
Article status Active
Shock operating IEC 60068-2-27 (15G)
Vibration resistence Sine vibration (based on IEC 60068-2-6), 5 ~ 25 Hz: ±1.6mm, 25 ~ 300 Hz: 4G, Sweep rate: 1 octave/min., 20 cycles, Random vibration (based on IEC 60068-2-64), 10 ~ 40 Hz: 0.0125g²/Hz, 40 ~ 100 Hz: 0.0125 → 0.002g²/Hz, 100 ~ 500 Hz: 0.002 g²/Hz, 500 ~ 2000 Hz: 0.002 → 1.3 x 10-4g²/Hz, Test time: 1hrs for each test
Industrial emissions EN 61000-6-4/A11: 2011
Industrial immunity EN 61000-6-2: 2019
Horisontal, Vertical
Product certifications CE, UL, cUL, FCC, RoHS, China RoHS, Reach
Power dissipation Max. 35 mA @ 5 VDC
Isolation I/O to Logic: Photocoupler isolation, I/O to Field Power: Non-Isolation
Field power Nominal supply voltage: 24 VDC, Voltage range: 60℃: 18~32 VDC, 70℃: 18~26.4 VDC
Weight 65 g
Module size 12x109x70 mm

Environmental

Mounting 35mm DIN rail
Operating temperature -20 ~ 60℃
Storage temperature -40 ~ 85℃
UL temperature -20 ~ 60℃
Relative humidity 5 ~ 90% non-condensing

Digital input module specifications

Indicators 8 green input status
Inputs per module 8 point SINK input
OFF state voltage 8.3 VDC @ 25℃
ON state current 3.0 mA / point @ 30 VDC
ON state voltage Nominal supply voltage: 24 VDC, Voltage range: 60℃: 18~32 VDC, 70℃: 18~26.4 VDC
Input filter Adjustable up to 10 ms
Nominal input impedance 10.2 kΩ typical
Input signal delay OFF to ON: 0.3 ms, ON to OFF: 0.3 ms
Common type 8 point / 1 COM

Digital output module specifications

Indicators 8 green output status
Outputs per module 8 point SOURCE output
Output current rating Max. 0.5 A per channel, Max. 6.0A per unit
Output signal delay OFF to ON: Max. 0.1 ms, ON to OFF: Max. 0.35 ms
Output voltage range Nominal supply voltage: 24 VDC, Voltage range: 60℃: 18~32 VDC, 70℃: 18~26.4 VDC
ON state voltage 0.3 VDC @ 25℃, 0.6 VDC @ 60℃
OFF state leakage current Max. 10 uA
Common type 8 point / 1 COM
Protection Over current limit: 2.2 A@ 25℃ per channel, Thermal Shutdown: 175℃ , Short circuit protection
Limited availability

GT-1428

Digital input/output


EOL - End Of Life:
-

LTB - Last Time Buy:
-

LTD - Last Time Delivery:
-

LTR - Last Time Repair:
-

Replacement Parts: