GT-3901
AC measurement
- 1 channel
- 3-phase 500VAC
- 24bit resolution
- Angle, Voltage, Current, Power, Energy, Frequency, Power Factors
- 45-65Hz
Facts
General description
Article number | 100-8069 |
Warranty | 2 year |
Article status | Active |
Shock operating | IEC 60068-2-27 (15G) |
Vibration resistence | Sine vibration (based on IEC 60068-2-6), 5 ~ 25Hz: ±1.6mm, 25 ~ 300Hz: 4G, Sweep rate: 1 octave/min., 20 cycles, Random vibration (based on IEC 60068-2-64), 10 ~ 40Hz: 0.0125g²/Hz, 40 ~ 100Hz: 0.0125 → 0.002g²/Hz, 100 ~ 500Hz: 0.002 g²/Hz, 500 ~ 2000Hz: 0.002 → 1.3 x 10-4g²/Hz, Test time: 1hrs for each test |
Industrial emissions | EN 61000-6-4/A11: 2011 |
Industrial immunity | EN 61000-6-2: 2005 |
Horisontal, Vertical | |
Product certifications | CE, FCC, RoHS, China RoHS, Reach |
Isolation | I/O to Logic: Photocoupler isolation, I/O to Field Power: Non-Isolation |
Field power | Supply voltage : 24Vdc nominal, Voltage range : 70℃ 18~26.4Vdc, 60℃ 18~32Vdc |
Weight | 60g |
Module size | 12x109x70mm |
Environmental
Mounting | 35mm DIN rail |
Operating temperature | -40 ~ 70℃, Degraded performance > 60℃ |
Storage temperature | -40 ~ 85℃ |
Relative humidity | 5 ~ 90% non-condensing |
Analog input module specifications
Calibration | Not Required |
Data format | 32 bit integer |
Indicators | 1 green status , 3 green Over Voltage or Under Voltage: VL1, VL2, VL3 , 3 green Over Current or Under Current: IL1, IL2, IL3 |
Inputs per module | 4 channels |
Module accuracy | Voltage = 0.5%, Current = 0.5%, Frequency = ±0.01Hz, Phase angle = ±0.3⁰ |
Resources
Manuals
Knowledge
- G series GT-3xxx, Filter Time (parameter)
- FnIO S-series and G-series , Serial number, Production date
- Shock resistance of G- and M-series (IEC 60068-2-27)
Product information
Brochures
Configuration files
Software
Drawings
Certificates
Limited availability
GT-3901
AC measurement
EOL - End Of Life:
-
LTB - Last Time Buy:
-
LTD - Last Time Delivery:
-
LTR - Last Time Repair:
-
Replacement Parts: