GT-3901

AC measurement

  • 1 channel
  • 3-phase 500VAC
  • 24bit resolution
  • Angle, Voltage, Current, Power, Energy, Frequency, Power Factors
  • 45-65Hz

Facts

General description

Article number 100-8069
Warranty 2 year
Article status Active
Shock operating IEC 60068-2-27 (15G)
Vibration resistence Sine vibration (based on IEC 60068-2-6), 5 ~ 25Hz: ±1.6mm, 25 ~ 300Hz: 4G, Sweep rate: 1 octave/min., 20 cycles, Random vibration (based on IEC 60068-2-64), 10 ~ 40Hz: 0.0125g²/Hz, 40 ~ 100Hz: 0.0125 → 0.002g²/Hz, 100 ~ 500Hz: 0.002 g²/Hz, 500 ~ 2000Hz: 0.002 → 1.3 x 10-4g²/Hz, Test time: 1hrs for each test
Industrial emissions EN 61000-6-4/A11: 2011
Industrial immunity EN 61000-6-2: 2005
Horisontal, Vertical
Product certifications CE, FCC, RoHS, China RoHS, Reach
Isolation I/O to Logic: Photocoupler isolation, I/O to Field Power: Non-Isolation
Field power Supply voltage : 24Vdc nominal, Voltage range : 70℃ 18~26.4Vdc, 60℃ 18~32Vdc
Weight 60g
Module size 12x109x70mm

Environmental

Mounting 35mm DIN rail
Operating temperature -40 ~ 70℃, Degraded performance > 60℃
Storage temperature -40 ~ 85℃
Relative humidity 5 ~ 90% non-condensing

Analog input module specifications

Calibration Not Required
Data format 32 bit integer
Indicators 1 green status , 3 green Over Voltage or Under Voltage: VL1, VL2, VL3 , 3 green Over Current or Under Current: IL1, IL2, IL3
Inputs per module 4 channels
Module accuracy Voltage = 0.5%, Current = 0.5%, Frequency = ±0.01Hz, Phase angle = ±0.3⁰

Limited availability

GT-3901

AC measurement


EOL - End Of Life:
-

LTB - Last Time Buy:
-

LTD - Last Time Delivery:
-

LTR - Last Time Repair:
-

Replacement Parts: